Vedere la pagina 46
Connecting Power
HP-AM456-9002A Rev 01
VMA-series Memory Array Installation and Service Guide
47
Connecting Power
WARNING! Powering down the system processor interrupts traffic and
causes loss of system logs and diagnostic data. To preserve this diagnostic data
it is recommended that the vincident and/or save log commands be
used prior to powering down the system.
It is recommended to reboot the system rather than powering down then up.
Using a syslog server also ensures logs are stored prior to any reboot or power
down. See Displaying and Setting System Log (Syslog) Options on page 71.
Power Requirements
The Memory Array has the following power requirements:
Connecting the AC Power Cords to the
System
WARNING! Only authorized, qualified, and trained personnel should attempt
to work on this equipment. Install the Memory Array with a 50 A maximum
branch circuit rating by an end-use application using a UL listed circuit breaker
rated at 50 A.
The Memory Array chassis has the AC power supplies installed prior to shipping.
Connect the AC power cord to either power receptacle on the Memory Array, or
both. Connecting a second power cord is for redundancy purposes.
The power supplies have an IEC-C20 male receptacle and accept an IEC-C19
female connector.
Caution: Consider the equipment connection to the supply circuit and the
effect that overloading the circuits might have on overcurrent protection and
supply wiring. Also consider the appropriate equipment nameplate ratings when
addressing this concern.
Table 3.3 Power Requirements
Item Requirement
Voltage Input Range 180 - 264VAC (1200 W)
90 - 264VAC (1000 W)
Frequency 47-63 Hz