HP VMA-series Memory Arrays Manuale Utente

Navigare online o scaricare Manuale Utente per Server HP VMA-series Memory Arrays. HP VMA-series Memory Arrays Installation and Service Guide Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 300
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Part Number: HP-AM456-9002A Rev 01
August 2011
Abstract
This document describes the installation and service procedures for the HP VMA-series Memory Array. This document
is intended for experienced service technicians. HP assumes that you are qualified in the servicing of computer
equipment, are trained in recognizing hazards in products with hazardous energy levels, and are familiar with
weight and stability precautions for rack installations.
HP VMA-series Memory Array
Installation and Service Guide
Vedere la pagina 0
1 2 3 4 5 6 ... 299 300

Sommario

Pagina 1 - HP VMA-series Memory Array

Part Number: HP-AM456-9002A Rev 01August 2011AbstractThis document describes the installation and service procedures for the HP VMA-series Memory Arra

Pagina 2 - LEGAL NOTICES

Table of Contents10VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01context controller . . . . . . . . . . . . . . . . . . .

Pagina 3 - Notice Description

Chapter 5 - Operating the System via the CLI100VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Upgrading the System Softwar

Pagina 4

Upgrading the System SoftwareHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide101Specify the path to the upgrade image using

Pagina 5

Chapter 5 - Operating the System via the CLI102VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01You are prompted to confirm

Pagina 6

Upgrading the System SoftwareHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1034. Specify the system processor to restart

Pagina 7

Chapter 5 - Operating the System via the CLI104VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. Set the system processor

Pagina 8

Upgrading the System SoftwareHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1054. While the system is rebooting, reboot yo

Pagina 9

Chapter 5 - Operating the System via the CLI106VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 10

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide107CHAPTER 6 Servicing the ArrayThis chapter describes how to service the M

Pagina 11

Chapter 6 - Servicing the Array108VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Guidelines for Servicing the SystemWARNIN

Pagina 12 - Table of Contents

Testing the LEDsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide109Testing the LEDsPerform functional tests on the LEDs ass

Pagina 13 - List of Figures

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide11System Context Commands . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 14

Chapter 6 - Servicing the Array110VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:3. At the context prompt, type:The

Pagina 15 - List of Tables

Replacing the FansHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide111Replacing the FansThe six fans are installed prior to

Pagina 16

Chapter 6 - Servicing the Array112VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Replacing the AC Power SuppliesThe redund

Pagina 17 - Document Organization

Replacing VIMMsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide113Replacing VIMMsThere are up to four spare VIMMs in the Me

Pagina 18 - Safety Icons

Chapter 6 - Servicing the Array114VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 015. Press firmly down on the latches until

Pagina 19 - Contacting HP

PART IIIHost UtilitiesChapter 7 Linux DriversChapter 8 Windows DriversChapter 9 Violin UtilitiesChapter 10 Performance Tuning and Troubleshooting

Pagina 21 - Product Overview

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide117CHAPTER 7 Linux DriversThis chapter describes the configuration of a dir

Pagina 22

Chapter 7 - Linux Drivers118VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Linux Drivers OverviewIn a direct-attached conf

Pagina 23 - VMA-series Overview

Installing Linux Driver PrerequisitesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide119In general, the configuration of a

Pagina 24 - Physical Components

Table of Contents12VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01show path . . . . . . . . . . . . . . . . . . . . . . .

Pagina 25 - System LEDs

Chapter 7 - Linux Drivers120VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01If a kernel was custom built from http://kernel

Pagina 26

Installing Linux DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide121Installing Linux DriversBefore installing the Li

Pagina 27 - Power Supplies

Chapter 7 - Linux Drivers122VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The script begins installing the driver, as sho

Pagina 28 - Figure 1.6 Fan Module

Installing Linux DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide123Installing Linux Drivers on Non-Running Linux Ke

Pagina 29 - Storage Interfaces

Chapter 7 - Linux Drivers124VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 018. When prompted to build the Linux driver type

Pagina 30

Loading and Unloading Linux DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide125Where N specifies the next available

Pagina 31 - System Specifications

Chapter 7 - Linux Drivers126VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. At the system prompt, navigate to the follow

Pagina 32 - Supported Operating Systems:

Installing the Violin UtilitiesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1275. To load the Linux driver, at the syste

Pagina 33

Chapter 7 - Linux Drivers128VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01For the complete syntax and usage details of ea

Pagina 34 - VIMM Types

Configuring Partitions and Storage DevicesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide129Configuring Partitions and Sto

Pagina 35 - VIMM Slot Locations

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide13List of FiguresFigure 1.1 Memory Array - Front View . . . . . . . . . . .

Pagina 36 - 42–Module Configuration

Chapter 7 - Linux Drivers130VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. At the Command prompt, type n to create a ne

Pagina 37 - Operation

Configuring Partitions and Storage DevicesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide131The command displays informati

Pagina 38

Chapter 7 - Linux Drivers132VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to the

Pagina 39 - Installing the Array

Configuring Partitions and Storage DevicesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1339. To unmount the file system,

Pagina 40

Chapter 7 - Linux Drivers134VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01<dump_opt>Specifies whether the device is

Pagina 41

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide135CHAPTER 8 Windows DriversThis chapter describes the installation of the

Pagina 42 - Equipment Rack

Chapter 8 - Windows Drivers136VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Windows Driver OverviewIn a direct-attached c

Pagina 43

Installing Windows DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide137Installing Windows DriversThe Windows Storport

Pagina 44

Chapter 8 - Windows Drivers138VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The Welcome to the Violin Array Storport Setu

Pagina 45

Installing Windows DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1397. To change the destination folder, click the

Pagina 46

List of Figures14VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Figure D.8 Chassis>Controller>Ethernet Context Comma

Pagina 47 - Power Requirements

Chapter 8 - Windows Drivers140VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The Completing the Violin Array Storport Setu

Pagina 48 - Connecting Equipment Ground

Installing Windows DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide14113.Click the Finish button.14.Reboot the host.

Pagina 49

Chapter 8 - Windows Drivers142VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The Update Driver Software: Unknown Device wi

Pagina 50 - Connecting the Serial Cable

Installing Windows DriversHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide143The Windows system installs the drivers. A con

Pagina 51 - Connecting the Ethernet Cable

Chapter 8 - Windows Drivers144VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. Select Add or Remove Programs. The Uninsta

Pagina 52 - Ethernet

Installing the Violin UtilitiesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide145These tools are used extensively during P

Pagina 53 - Host Computer

Chapter 8 - Windows Drivers146VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The License Agreement window appears.6. Selec

Pagina 54 - Memory Gateway

Installing the Violin UtilitiesHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide1478. To change the destination folder, clic

Pagina 55

Chapter 8 - Windows Drivers148VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Expand the Disk Drives node to view the Memor

Pagina 56 - Powering up the Memory Array

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide149CHAPTER 9 Violin UtilitiesThis chapter describes the Violin Utilities us

Pagina 57 - Configuring the Array

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide15List of TablesTable 1.1 Front LED Descriptions . . . . . . . . . . . . .

Pagina 58 - Memory Array Default Settings

Chapter 9 - Violin Utilities150VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Understanding the Violin UtilitiesThe Violin

Pagina 59 - Connecting to the CLI

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide151• vcounts on page 151• veeprom on page 153• vh

Pagina 60

Chapter 9 - Violin Utilities152VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01ReturnsThe vcounts utility returns the follo

Pagina 61

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide153veepromThe veeprom utility displays the Memory

Pagina 62 - Changing the Admin Password

Chapter 9 - Violin Utilities154VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Windows ExampleThe veeprom utility returns i

Pagina 63

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide155The Linux example returns the following inform

Pagina 64 - Changing the Hostname

Chapter 9 - Violin Utilities156VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01You must log in as root on the Linux host co

Pagina 65 - Enabling DHCP

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide157ReturnsThe vinfo utility returns the following

Pagina 66 - Disabling DHCP

Chapter 9 - Violin Utilities158VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01vpartialThe vpartial utility displays the nu

Pagina 67 - Configuring the DNS Name

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide159vringThe vring utility debugs the internal Mem

Pagina 68 - Ethernet 0

List of Tables16VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Table D.9 Controller Context Commands . . . . . . . . . .

Pagina 69 - Setting the DNS Mode

Chapter 9 - Violin Utilities160VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01ParametersExampleThe vring utility returns i

Pagina 70

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide161ExampleThe vstat utility returns information s

Pagina 71 - Syslog Host

Chapter 9 - Violin Utilities162VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01vupdate_tzThe vupdate_tz utility updates the

Pagina 72

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide163ExampleThe vupdate_tz utility returns informat

Pagina 73

Chapter 9 - Violin Utilities164VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxperf_testFor a discussion of using the

Pagina 74 - Formatting the Memory Array

Violin Utilities ReferenceHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide165ExampleBy default, the perf_test accesses the

Pagina 75

Chapter 9 - Violin Utilities166VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The perf_test utility returns information si

Pagina 76 - Connecting via Telnet

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide167CHAPTER 10 Performance Tuning and TroubleshootingThis chapter provides a

Pagina 77

Chapter 10 - Performance Tuning and Troubleshooting168VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Performance Tuning an

Pagina 78

Flash-Layer Performance TuningHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide169While these tests are running, use operati

Pagina 79 - Setting the Number of Columns

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide17PrefaceThis document describes how to install and service the Memory Arra

Pagina 80

Chapter 10 - Performance Tuning and Troubleshooting170VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01system, do so for tra

Pagina 81

Flash-Layer Performance TuningHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide171between 512 and 3584 for transfer size, si

Pagina 82 - Setting the Pagination Mode

Chapter 10 - Performance Tuning and Troubleshooting172VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 011. If the disk you ar

Pagina 83

Network-Layer Performance TestingHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide173• Performance Testing Using perf_test o

Pagina 84 - HH:MM:SS

Chapter 10 - Performance Tuning and Troubleshooting174VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Performance Testing U

Pagina 85

Network-Layer Performance TestingHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide175The following table describes the optio

Pagina 86

Chapter 10 - Performance Tuning and Troubleshooting176VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Block SizeConsider th

Pagina 87

Network-Layer Performance TestingHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide177• Random reads at 4kB block size:(-R) (

Pagina 88 - Retrieving the MAC Address

Chapter 10 - Performance Tuning and Troubleshooting178VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01In the following exam

Pagina 89

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide179APPENDIX A Product ModelsThis appendix describes the differences between

Pagina 90 - RAID Group

Preface18VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01– Chapter 7, Linux Drivers—Describes how to install, use, and remo

Pagina 91

Appendix A - Product Models180VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 92

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide181APPENDIX B Compliance InformationThis appendix contains the following co

Pagina 93

Appendix B - Compliance Information182VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Regulatory InformationFor your protec

Pagina 94 - Displaying Fan Status

Lithium Battery CautionHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide18380004) is available (or supplied with memory addi

Pagina 95

Appendix B - Compliance Information184VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Disposal of Waste Equipment by Users

Pagina 96 - Displaying the System Log

Japan Radio Frequency Interference VCCIHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide185Japan Radio Frequency Interferenc

Pagina 97 - Displaying the Messages Log

Appendix B - Compliance Information186VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 98 - Canceling a Scheduled Reboot

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide187APPENDIX C Alarm ReferenceThis chapter describes how to diagnose Memory

Pagina 99

Appendix C - Alarm Reference188VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Understanding Memory Array AlarmsThe Memory

Pagina 100 - Upgrading the System Software

Understanding Memory Array AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide189during bootup because the data plane is

Pagina 101 - Using SCP

SecurityHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide19Typographical ConventionsThe table below summarizes the typograph

Pagina 102 - Length

Appendix C - Alarm Reference190VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01show system messages CommandThe show system

Pagina 103

Service-Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide191• Equipment Service-Affecting Alarms on page 191

Pagina 104

Appendix C - Alarm Reference192VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01To clear the alarm, replace the non-function

Pagina 105 - Displaying the Upgrade Path

Service-Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide193AC Power Failure, Shutting Down AlarmThe AC Powe

Pagina 106 - HP-AM456-9002A Rev 01

Appendix C - Alarm Reference194VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01RAID Group Faulted AlarmThe RAID Group Fault

Pagina 107 - Servicing the Array

Service-Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide195This is a nonrecoverable error. Contact HP Custo

Pagina 108 - ESD Precautions

Appendix C - Alarm Reference196VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01VIMM Service-Affecting AlarmsThere are four

Pagina 109 - Testing the System LEDs

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide197Unless noted otherwise, non-service affectin

Pagina 110 - Testing the VIMM LEDs

Appendix C - Alarm Reference198VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01To clear the alarm, check fan operation, the

Pagina 111 - Replacing the Fans

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide199Fan Running Too Slowly AlarmThe Fan Running

Pagina 112 - PORT 1 PORT 2

2VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01LEGAL NOTICES© Copyright 2011 Hewlett-Packard Development Company, L.P.The

Pagina 113 - Replacing VIMMs

Preface20VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01• Call 1-800-HP-INVENT (1-800-474-6836). This service is available

Pagina 114

Appendix C - Alarm Reference200VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Flash Sequence Number Mismatch AlarmThe Flas

Pagina 115 - Host Utilities

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide201Port Is Not Running at the Maximum Data Rate

Pagina 116

Appendix C - Alarm Reference202VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01RAID Non-Service Affecting AlarmsThere are f

Pagina 117 - Linux Drivers

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide203• Excessive ECC Errors on VIMM Alarm on page

Pagina 118 - Linux Drivers Overview

Appendix C - Alarm Reference204VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Failed to Validate Configuration of VIMMS, R

Pagina 119 - Kernel Development Package

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide205The show system status command and the alarm

Pagina 120 - Installing Linux Drivers

Appendix C - Alarm Reference206VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 011. Check for any airflow restrictions, inclu

Pagina 121

Non-Service Affecting AlarmsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide207VIMM Isolated AlarmThe VIMM Isolated alarm i

Pagina 122

Appendix C - Alarm Reference208VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 123

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide209APPENDIX D CLI ReferenceThis appendix lists and describes the available

Pagina 124

PART IProduct OverviewChapter 1 VMA-series OverviewChapter 2 Violin Intelligent Memory Modules

Pagina 125 - Removing the Linux Drivers

Appendix D - CLI Reference210VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01• In-memory Context Commands on page 281• Cate

Pagina 126

Context NavigationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide211Context NavigationThe CLI consists of a context hierar

Pagina 127 - Unloading the Linux Driver

Appendix D - CLI Reference212VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Navigate to the context level then enter the c

Pagina 128

General CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide213General CommandsThe table below describes the general co

Pagina 129

Appendix D - CLI Reference214VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:clearClears the system log file.Syntaxcl

Pagina 130

General CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide215Where:The available commands and sublevels are different

Pagina 131 - /dev/vtmsa<n>

Appendix D - CLI Reference216VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:Higher usable percentages provide more u

Pagina 132

General CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide217The command displays information similar to the followin

Pagina 133 - Partitions

Appendix D - CLI Reference218VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01If you do not specify the time delay, you are

Pagina 134

General CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide219Where:ExampleTo show information for the chassis board 0

Pagina 136 - Installing Prerequisites

Appendix D - CLI Reference220VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01SyntaxtopExampleIf you are at the Chassis boar

Pagina 137 - Installing Windows Drivers

Chassis Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide221Chassis Context CommandsFigure D.2 Chassis Cont

Pagina 138 - Click the Next button

Appendix D - CLI Reference222VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxcontext controllerThe system prompt chan

Pagina 139

Board 0 Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide223Board 0 Context CommandsFigure D.3 Chassis>B

Pagina 140 - Chapter 8 - Windows Drivers

Appendix D - CLI Reference224VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:The system prompt changes to the followi

Pagina 141 - (driver-storport-Dx.x.x.zip)

Board 0 Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide225show flash-scrubbingDisplays the status of flash

Pagina 142

Appendix D - CLI Reference226VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:enabled Enables the write buffer on the

Pagina 143 - Removing the Windows Drivers

Slot Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide227Slot Context CommandsFigure D.4 Chassis>Board 0

Pagina 144

Appendix D - CLI Reference228VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 145

Slot Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide229The command displays information similar to the fol

Pagina 146

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide23CHAPTER 1 VMA-series OverviewThis chapter introduces the VMA-series Memor

Pagina 147

Appendix D - CLI Reference230VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01VIMM Context CommandsFigure D.5 Chassis>Bo

Pagina 148 - Removing the Violin Utilities

VIMM Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide231WARNING! Before removing the VIMM, change the admin

Pagina 149 - Violin Utilities

Appendix D - CLI Reference232VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01environment temperature 66C (OK) s

Pagina 150 - Violin Utilities Reference

VIMM-summary Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide233VIMM-summary Context CommandsFigure D.6 Ch

Pagina 151

Appendix D - CLI Reference234VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Under normal conditions for a fully-populated

Pagina 152

VIMM-summary Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide235oper-down-vimm-idsIndicates the IDs of the

Pagina 153

Appendix D - CLI Reference236VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Controller Context CommandsFigure D.7 Chassis

Pagina 154

Controller Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide237Syntaxshow serial-speedcontext ethernet 0Move

Pagina 155

Appendix D - CLI Reference238VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Ethernet 0 Context CommandsFigure D.8 Chassis

Pagina 156

Ethernet 0 Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide239Syntaxset dhcp {enabled | disabled}Where:Use

Pagina 157

Chapter 1 - VMA-series Overview24VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01FeaturesThe Memory Array:• Combines standa

Pagina 158

Appendix D - CLI Reference240VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxset dns-config {manual | auto}Where: Use

Pagina 159

Ethernet 0 Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide241Where:Use the save config command to save the

Pagina 160

Appendix D - CLI Reference242VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01resetResets the Ethernet port.SyntaxresetExamp

Pagina 161

Fan-tray Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide243Fan-tray Context Commands Figure D.9 Chassis&g

Pagina 162

Appendix D - CLI Reference244VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Fan Context CommandsFigure D.10 Chassis>Fa

Pagina 163

CLI Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide245CLI Context CommandsFigure D.11 CLI Context LevelTh

Pagina 164 - Option Description

Appendix D - CLI Reference246VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01set edit-modeSets the command line editing mod

Pagina 165

CLI Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide247Syntaxset lines <n>Where:set paginationEnables

Pagina 166

Appendix D - CLI Reference248VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 167

CLI Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide249The command displays information similar to the foll

Pagina 168

Physical ComponentsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide25The power button on the front of the array can be used

Pagina 169

Appendix D - CLI Reference250VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 170

RAID Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide251RAID Context CommandsFigure D.12 RAID Context Leve

Pagina 171

Appendix D - CLI Reference252VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information shown below:.

Pagina 172

RAID Group Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide253RAID Group Context CommandsFigure D.13 RAID&

Pagina 173

Appendix D - CLI Reference254VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays the following information

Pagina 174

Maps Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide255Maps Context Commands Figure D.14 RAID>Group>

Pagina 175

Appendix D - CLI Reference256VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:group-number Indicates the RAID group ID

Pagina 176

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide257System Context CommandsFigure D.15 System Contex

Pagina 177

Appendix D - CLI Reference258VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01cancel rebootCancels a currently scheduled reb

Pagina 178

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide259Syntaxclear logExampleTo clear the system log, at

Pagina 179 - Product Models

Chapter 1 - VMA-series Overview26VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Front LEDsThe front LEDs are illustrated i

Pagina 180 - Appendix A - Product Models

Appendix D - CLI Reference260VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxcontext boot-paramsThe system prompt cha

Pagina 181 - Compliance Information

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide261context statusMoves into the system Status contex

Pagina 182

Appendix D - CLI Reference262VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxcontext versionThe system prompt changes

Pagina 183 - Cabinet Safety Precautions

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide263Syntaxset admin <password>You will be promp

Pagina 184 - European Union RFI Statement

Appendix D - CLI Reference264VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01set boot-paramsSets the system boot parameters

Pagina 185 - Australia C-Tick Label

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide265The command displays information similar to the f

Pagina 186

Appendix D - CLI Reference266VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01set nameSets the hostname of the system. When

Pagina 187 - Alarm Reference

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide267Where:show clock-sourceDisplays the current clock

Pagina 188 - Interpreting Alarm LEDs

Appendix D - CLI Reference268VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 189 - Message Commands

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide269The command displays information similar to the f

Pagina 190 - Service-Affecting Alarms

Physical ComponentsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide27Rear LEDsThe rear LEDs are illustrated in the figure b

Pagina 191

Appendix D - CLI Reference270VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 192 - Port Service-Affecting Alarms

System Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide271The command displays information similar to the f

Pagina 193 - RAID Service-Affecting Alarms

Appendix D - CLI Reference272VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 194 - Appendix C - Alarm Reference

Alarms Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide273Alarms Context CommandsFigure D.16 System>Ala

Pagina 195

Appendix D - CLI Reference274VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 196 - Non-Service Affecting Alarms

Boot-params Context LevelHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide275Boot-params Context LevelFigure D.17 System>

Pagina 197

Appendix D - CLI Reference276VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01show stagger-mem-clearDisplays the current sta

Pagina 198

LED-state Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide277LED-state Context CommandsFigure D.18 System&

Pagina 199

Appendix D - CLI Reference278VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 200 - 1 or 2. The Alarm LED is not

Logging Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide279Logging Context Commands Figure D.19 System>

Pagina 201

Chapter 1 - VMA-series Overview28VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The power supplies convert the incoming AC

Pagina 202

Appendix D - CLI Reference280VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01context syslogMoves into the Syslog context le

Pagina 203

In-memory Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide281In-memory Context CommandsFigure D.20 System&

Pagina 204

Appendix D - CLI Reference282VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01ExampleWhen navigating to the util category co

Pagina 205

In-memory Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide283set default-levelSets the level of messages st

Pagina 206

Appendix D - CLI Reference284VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Syntaxshow default-levelThe command displays i

Pagina 207 - 1) or bottom (2)

Category Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide285Category Context CommandsFigure D.21 System>

Pagina 208

Appendix D - CLI Reference286VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:show levelDisplays the logging level of

Pagina 209 - CLI Reference

Syslog Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide287Syslog Context CommandsFigure D.22 System>Log

Pagina 210 - Appendix D - CLI Reference

Appendix D - CLI Reference288VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Where:Use the save config command to save the

Pagina 211 - Typing CLI Commands

Syslog Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide289show serviceDisplays the status of the service th

Pagina 212

Connectivity and Interfaces OverviewHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide29Refer to Figure 1.2 for interface loc

Pagina 213 - General Commands

Appendix D - CLI Reference290VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Status Context CommandsFigure D.23 System>

Pagina 214 - <context_level>

Status Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide291The command displays information similar to the f

Pagina 215

Appendix D - CLI Reference292VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 216

Status Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide293The command displays information similar to the f

Pagina 217

Appendix D - CLI Reference294VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Sw-upgrade Context CommandsFigure D.24 System

Pagina 218

Sw-upgrade Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide295set activeSets the specified partition in fla

Pagina 219

Appendix D - CLI Reference296VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01The command displays information similar to th

Pagina 220

Uptime Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide297Uptime Context CommandsFigure D.25 System>Upt

Pagina 221 - Chassis Context Commands

Appendix D - CLI Reference298VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Version Context CommandsFigure D.26 System>

Pagina 222

Version Context CommandsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide299controller version info: 12954_x8a @ 05/2

Pagina 223 - Board 0 Context Commands

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide3COMPLIANCE INFORMATIONNotice DescriptionFCC Class A Compliance “This devic

Pagina 224

Chapter 1 - VMA-series Overview30VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Once a Memory Array is connected to a host

Pagina 225

Appendix D - CLI Reference300VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 226

System SpecificationsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide31System SpecificationsThe table below lists the Memor

Pagina 227 - Slot Context Commands

Chapter 1 - VMA-series Overview32VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01See Connecting the PCIe Cable to a Host Co

Pagina 228

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide33CHAPTER 2 Violin Intelligent Memory ModulesThis chapter describes the Vio

Pagina 229

Chapter 2 - Violin Intelligent Memory Modules34VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Violin Intelligent Memory Mo

Pagina 230 - VIMM Context Commands

VIMM ConfigurationsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide35Memory arrays store up to 64, 128, 256, or 512 GB of d

Pagina 231

Chapter 2 - Violin Intelligent Memory Modules36VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 0142–Module ConfigurationFor t

Pagina 232

PART IIOperationChapter 3 Installing the ArrayChapter 4 Configuring the ArrayChapter 5 Operating the System via the CLIChapter 6 Servicing the Array

Pagina 234

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide39CHAPTER 3 Installing the ArrayThis chapter describes how to install the M

Pagina 235 - Output Description

4VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01

Pagina 236 - Controller Context Commands

Chapter 3 - Installing the Array40VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Installation and Configuration OverviewMe

Pagina 237

Installation and Configuration OverviewHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide41Chapter 9, Violin Utilities. Phase

Pagina 238 - Ethernet 0 Context Commands

Chapter 3 - Installing the Array42VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Rack-Mounting the ChassisInstalling the M

Pagina 239

Rack-Mounting the ChassisHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide43Figure 3.2 Installing the Memory Array into a R

Pagina 240

Chapter 3 - Installing the Array44VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01To install the cable management arm:1. At

Pagina 241

Rack-Mounting the ChassisHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide45Figure 3.4 Installing the Cable Holder

Pagina 242

Chapter 3 - Installing the Array46VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Connecting the PCIe Cable to the Memory A

Pagina 243 - Fan-tray Context Commands

Connecting PowerHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide47Connecting PowerWARNING! Powering down the system process

Pagina 244 - Fan Context Commands

Chapter 3 - Installing the Array48VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Note: The AC power cords are not a standa

Pagina 245 - CLI Context Commands

Connecting PowerHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide492. Route the equipment ground cable to the rear of the eq

Pagina 246

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide5Table of ContentsList of Figures . . . . . . . . . . . . . . . . . . . .

Pagina 247

Chapter 3 - Installing the Array50VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Connecting Management NetworkConnecting t

Pagina 248

Connecting Management NetworkHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide51Figure 3.7 Connecting the Serial Cable to t

Pagina 249

Chapter 3 - Installing the Array52VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Figure 3.9 Connecting the Ethernet Cable

Pagina 250 - Cancels the oam_cli session

Connecting the PCIe Cable to a Host Computer or Memory GatewayHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide53Connecting

Pagina 251 - RAID Context Commands

Chapter 3 - Installing the Array54VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Memory GatewayThe steps for connecting th

Pagina 252

Routing the Cables onto the Cable Management ArmHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide55Routing the Cables onto t

Pagina 253 - RAID Group Context Commands

Chapter 3 - Installing the Array56VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Powering up the Memory ArrayAfter connect

Pagina 254

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide57CHAPTER 4 Configuring the ArrayWhen the Memory Array is first powered on,

Pagina 255 - Maps Context Commands

Chapter 4 - Configuring the Array58VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Memory Array Default SettingsThe Memory

Pagina 256

Connecting to the CLIHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide59Connecting to the CLILogging into the CLI via the Se

Pagina 257 - System Context Commands

Table of Contents6VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Connecting the PCIe Cable to the Memory Array. . . . . .

Pagina 258

Chapter 4 - Configuring the Array60VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Logging in to the CLI via a Linux host c

Pagina 259

Connecting to the CLIHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide619. At this point, you are connected to the CLI of th

Pagina 260

Chapter 4 - Configuring the Array62VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Changing the Default System SettingsTabl

Pagina 261

Changing the Default System SettingsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide63You will be prompted to enter a new p

Pagina 262

Chapter 4 - Configuring the Array64VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Note: When you change the IP address of

Pagina 263

Configuring DHCP SettingsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide65Configuring DHCP SettingsConfigure several DHCP

Pagina 264

Chapter 4 - Configuring the Array66VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Disabling DHCPDisable DHCP to manually s

Pagina 265

Configuring Domain Name System (DNS)HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide67Configuring Domain Name System (DNS)T

Pagina 266

Chapter 4 - Configuring the Array68VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Configuring the DNS Search Domain NameWh

Pagina 267

Configuring Domain Name System (DNS)HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide693. At the Ethernet 0 context prompt,

Pagina 268

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide7Displaying the System Date and Time . . . . . . . . . . . . . . . . . . .

Pagina 269

Chapter 4 - Configuring the Array70VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Verifying the Ethernet ConnectionThe Eth

Pagina 270

Displaying and Setting System Log (Syslog) OptionsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide71Displaying and Setting

Pagina 271

Chapter 4 - Configuring the Array72VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Setting the IP Address for the Syslog Ho

Pagina 272

Displaying and Setting System Log (Syslog) OptionsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide73The command displays in

Pagina 273 - Alarms Context Commands

Chapter 4 - Configuring the Array74VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Formatting the Memory ArrayNote: The arr

Pagina 274

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide75CHAPTER 5 Operating the System via the CLIThe CLI resides on the Memory A

Pagina 275 - Boot-params Context Level

Chapter 5 - Operating the System via the CLI76VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Connecting to the CLIConnect

Pagina 276

Connecting to the CLIHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide77Note: To connect to the Memory Array from a Windows

Pagina 277 - LED-state Context Commands

Chapter 5 - Operating the System via the CLI78VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01[root@lab5 ~]# telnet 10.10.2

Pagina 278

Displaying and Setting the CLI Window OptionsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide79Displaying and Setting the C

Pagina 279 - Logging Context Commands

Table of Contents8VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Loading Linux Drivers Manually . . . . . . . . . . . . .

Pagina 280

Chapter 5 - Operating the System via the CLI80VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Displaying the Command Line E

Pagina 281 - In-memory Context Commands

Displaying and Setting the CLI Window OptionsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide81The command displays informa

Pagina 282

Chapter 5 - Operating the System via the CLI82VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Displaying the Pagination Mod

Pagina 283

Displaying and Setting System InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide83Displaying and Setting System In

Pagina 284

Chapter 5 - Operating the System via the CLI84VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01If the VIMM configuration is

Pagina 285 - Category Context Commands

Displaying and Setting System InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide85Displaying the System Date and T

Pagina 286

Chapter 5 - Operating the System via the CLI86VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Displaying the System Clock S

Pagina 287 - Syslog Context Commands

Displaying and Setting System InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide87The command displays information

Pagina 288

Chapter 5 - Operating the System via the CLI88VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 012. Navigate to the Ethernet 0

Pagina 289

Displaying and Setting System InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide891. From the CLI prompt, type:2.

Pagina 290 - Status Context Commands

HP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide9Network Connected Equipment . . . . . . . . . . . . . . . . . . . . . . .

Pagina 291

Chapter 5 - Operating the System via the CLI90VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. At the Ethernet 0 context

Pagina 292

Displaying and Setting System InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide91Displaying the Spare VIMM Inform

Pagina 293

Chapter 5 - Operating the System via the CLI92VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Displaying and Setting Hardwa

Pagina 294 - Sw-upgrade Context Commands

Displaying and Setting Hardware InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide93Displaying the Number of VIMMs

Pagina 295

Chapter 5 - Operating the System via the CLI94VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 013. At the context prompt, typ

Pagina 296

Displaying and Setting Hardware InformationHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide95The command displays informati

Pagina 297 - Uptime Context Commands

Chapter 5 - Operating the System via the CLI96VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Displaying Alarms and LogsDis

Pagina 298 - Version Context Commands

Displaying Alarms and LogsHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide97The command displays information similar to the

Pagina 299

Chapter 5 - Operating the System via the CLI98VMA-series Memory Array Installation and Service GuideHP-AM456-9002A Rev 01Rebooting the Memory ArrayWhe

Pagina 300

Rebooting the Memory ArrayHP-AM456-9002A Rev 01VMA-series Memory Array Installation and Service Guide992. Navigate to the System context level. At the

Commenti su questo manuale

Nessun commento