Pagina 1 - INSTALLATION

GENERATING SETINSTALLATIONMANUAL

Pagina 2 - FOREWORD

76.2 Exhaust Pipe Flexible SectionA flexible connection between the manifold and theexhaust piping system should be used to preventtransmitting engine

Pagina 3 - TABLE OF CONTENTS

8Excessive restriction in the exhaust system can beavoided by proper design and construction. Tomake sure you will avoid problems related toexcessive

Pagina 4 - LOCATION

97. EXHAUST SILENCINGExcessive noise is objectionable in most locations.Since a large part of the generating set noise isproduced in the engine's

Pagina 5 - MOUNTING

108. SOUND ATTENUATIONIf noise level must be limited, it should be specifiedin terms of a sound pressure level at a givendistance from the generator e

Pagina 6 - 5. VENTILATION

11FIG 9.1 SET MOUNTED RADIATOR DISCHARGING THROUGH OUTSIDE WALLSet mounted radiators are of two types. One type isused with the cooling fan mounted

Pagina 7 - 5.2 Ventilators

12FIG 9.2 REMOTE RADIATOR CONNECTED DIRECTLY FIG 9.3 REMOTE RADIATOR ISOLATED FROMTO ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM BY HEATEXCHANGER9.2 R

Pagina 8 - 5.4 Exit Ventilator Size

13 FIG 9.4 TYPICAL HEAT EXCHANGER INSTALLATION FIG 9.5 HEAT EXCHANGER COOLING SYSTEM9.5 Antifreeze ProtectionIf the engine is to be ex

Pagina 9 - 6. ENGINE EXHAUST

1410.2 Remote Fuel SystemsThree types of remote fuel systems arerecommended by the manufacturer:Fuel System 1: Installations where the bulk fueltank

Pagina 10 - Restriction

15With this system, the basetank must include anoverflow via the return line, sealed fuel level gaugesand no manual fill facility. All other connectio

Pagina 11

16Flexible piping should be used to connect to theengine to avoid damage or leaks caused by enginevibration.The fuel delivery line should pick up fuel

Pagina 12 - 7. EXHAUST SILENCING

iiFOREWORDThis installation manual will guide you to the factors to be considered in theinstallation of your diesel generator system. It discusses l

Pagina 13 - 9. ENGINE COOLING

1711.SELECTING FUELSFOR STANDBY DEPENDABILITYThe types of fuels available for diesel engines, varyfrom highly volatile jet fuels and kerosene to thehe

Pagina 14

18Other solutions are to add inhibitors to the fuel orto obtain greater turnover by using the fuel forother purposes. A gum inhibitor added to diesel

Pagina 15 - 9.2 Remote Radiator

1912. TABLES AND FORMULAS FOR ENGINEERING STANDBY GENERATINGSETSTable 1. Length EquivalentsUnit Microns Meters Kilometres Inches Feet Yards Miles1 Mic

Pagina 16 - 10. FUEL SUPPLY

20Table 4. Volume and Capacity EquivalentsUnit Inches3Feet3Yards3Meters3US LiquidGallonsImperialGallonsLitres1 Inch31 0.000579 0.0000214 0.0000164 0.0

Pagina 17 - 10.2 Remote Fuel Systems

21Table 7. Conversions for Measurements of WaterUnit Feet3Pounds Gal(U.S)Gal(IMP)Litres Head(Ft)lb/in² Ton/Ft² Head(Meters)Ft³/Min Gal.(U.S)/HrFeet31

Pagina 18 - 10.4 Fuel Lines

22Table 9. Conversions of Units of FlowUnitU.SGallons/MinuteMillion U.SGallons/DayFeet3/Second Meters3/Hour Litres/Second1 U.SGallon/Minute1 0.001440

Pagina 19 - 10.5 Day Tank Capacity

23Table 12. Electrical formulaeDesired Data Single Phase Three-Phase Direct CurrentKilowatts (kW) I x V x PF 1000 3 x I x V x PF1000 I x

Pagina 20 - DEPENDABILITY

24TABLE 13. kVA/kW AMPERAGE AT VARIOUS VOLTAGES(0.8 Power Factor)kVA kW 208V 220V 240V 380V 400V 440V 460V 480V 600V 2400V 33000V 4160V6.3 5 17.5 16.5

Pagina 21

25Conversions of Centigrade and FahrenheitWater freezes at 0 ºC (32ºF) Water boils at 100 ºC (212ºF)ºF= ( 1.8 x ºC ) + 32 ºC = 0.5555 ( ºF - 3

Pagina 22 - Table 3. Mass Equivalents

2613. GLOSSARY OF TERMSALTERNATING CURRENT (AC) - A current which periodically reverses in direction and changes its magnitudeas it flows through a co

Pagina 23

TABLE OF CONTENTSPAGE1. INSTALLATION FACTORS2. MOVING THE GENERATING SET3. GENERATING SET LOCATION4. GENERATING SET MOUNTING5. VENTILATION6. ENGINE EX

Pagina 24

27CURRENT (I) - The rate of flow of electricity. DC flows from negative to positive. AC alternates in direction. Thecurrent flow theory is used conven

Pagina 25

28kW - 1,000 Watts (Real power). Equal to KVA multiplied by the power factor.POWER - Rate of performing work, or energy per unit of time. Mechanical p

Pagina 26 - Table 12. Electrical formulae

29TELEPHONE INFLUENCE FACTOR (TIF) - The telephone influence factor of a synchronous generator is ameasure of the possible effect of harmonics in the

Pagina 27

276-851 INSTALL.DOC/0601GROUP HEADQUARTERSOld Glenarm RoadLarne, Co. Antrim BT40 1EJNorthern Ireland, United KingdomTelephone: (44) 028 2826 1000Fax:

Pagina 28 - Piston Travel

11. INSTALLATION FACTORSOnce the size of the generating set and the requiredassociated control panel and switchgear have beenestablished, plans for in

Pagina 29 - 13. GLOSSARY OF TERMS

24. GENERATING SET MOUNTINGThe generating set will be shipped assembled on arigid base that precisely aligns the alternator andengine and needs merely

Pagina 30

35. VENTILATIONAny internal combustion engine requires a liberalsupply of cool, clean air for combustion. If the airentering the engine intake is too

Pagina 31

45.2 VentilatorsTo bring in fresh air, there should be an inletventilator opening to the outside or at least anopening to another part of the building

Pagina 32

55.3 Inlet Ventilator SizeBefore calculating the inlet ventilator size, it isnecessary to take into account the radiator coolingair flow requirements

Pagina 33 - 276-851 INSTALL.DOC/0601

66. ENGINE EXHAUSTEngine exhaust must be directed to the outsidethrough a properly designed exhaust system thatdoes not create excessive back pressure