AC line voltage requirements
This section lists the AC power recommendations for each power cord. Each DKC or DKU has two
or four power cords. In case of a failure of the power source for one cord, the power requirements,
and therefore the current requirement for the remaining power cord, will double.
For details on electrical specifications, cabling, and connectors, see the HP StorageWorks XP12000
Disk Array Site Preparation Guide.
Table 6 50-amp, 50 or 60 Hz single-phase DKC AC voltage specifications
240 VAC230 VAC220 VAC
208 VAC 60 Hz
only
200 VACParameter
18.819.620.521.722.6
Rated line current per power cord
(amps RMS)
22222Number of power cords
50A50A50A50A50ARecommended circuit breakers
22222Number of circuit breakers
Table 7 30-amp, 50 or 60 Hz, single-phase DKC AC voltage specifications
240 VAC230 VAC220 VAC
208 VAC 60 Hz
only
200 VACParameter
9.49.810.310.911.3
Rated line current per power cord
(amps RMS)
44444Number of power cords
30A30A30A30A30ARecommended circuit breakers
44444
Number of circuit breakers. Units with
only two power cords require only
two circuit breakers.
Table 8 30-amp, 50 or 60 Hz, three-phase DKC AC voltage specifications
415
VAC
400
VAC
380
VAC
240
VAC
230
VAC
220
VAC
208 VAC 60 Hz
only
200
VAC
Parameter
6.36.56.910.911.311.912.513
Rated line current
per power cord
(amps RMS)
22222222
Number of power
cords
30A30A30A30A30A30A30A30A
Recommended
circuit breakers
XP12000 Disk Array Owner's Guide 33