Chapter 2 Controls, Ports, and Indicators
8
In North American, use a 20-amp-minimum circuit with one NEMA AB1
class 14B breaker for each 16-amp Power Distribution Unit (PDU).
In Europe:
For a single NetServer in a rack, use a 15-amp-minimum circuit with
one IEC MCB C-type breaker for each 16-amp PDU.
For multiple NetServers in a rack, use a 15-amp-minimum circuit with
one IEC MCB D-type breaker for each 16-amp power distribution
unit.
Each 16-amp PDU can accommodate a maximum of two NetServers.
When the proper power supply is available, connect the NetServer to the AC
power source.
Power-On Tests
The NetServer runs a set of diagnostic tests when it is first connected to a power
source. If the NetServer passes the tests, you will see:
HP NetServer
LH 4
If the NetServer does not pass the tests, you will see:
<error code>
Display now?
Press Enter to view the error message. Write the error message down and refer to
"POST Codes" in Chapter 12, "Troubleshooting."